System design

What Is a Fan Coil Unit? Types, Sizes and How They Work (UK)

Fan coil units explained: cassette, ducted, floor and wall types with makers' capacity, airflow and noise data, 2-pipe vs 4-pipe, EC motors, and fan coil vs VRF.

  • 13 min read
  • Updated 28 November 2026
  • 15 named sources

By Local AC Installers Editorial Team · Published · Updated

A fan coil unit is a box with a fan, a coil and a filter: the fan pulls room air across the coil, and chilled or hot water inside the coil cools or heats that air. In UK offices and hotels the term usually means a water unit fed from a central chiller, heat pump or boiler, fitted as a ceiling cassette, a concealed ducted box above the ceiling, a floor console or a high-wall unit. On the makers' data sheets we read on 28 November 2026, single units run from about 1.3 to 11 kW of cooling and 200 to 1,800 m³/h of air, with large ducted models up to about 25 kW. A domestic split's indoor unit is also a fan and a coil, but it carries refrigerant, so make any quote say which one it means.

Wall-mounted air conditioning in a UK home

A cassette grille in a landlord ceiling

Stand under a ceiling grille in a fitted office and the word fan coil can mean two machines. On a domestic or shop split, the wall unit, cassette, floor console or ducted indoor is a fan coil in the broad sense: a fan, a coil, a filter and a drain. The coil carries refrigerant. An F-gas certified company handles that circuit. The outdoor unit rejects the heat in cooling, or collects it in heating. Energy Saving Trust describes that air-to-air pattern for homes. On a landlord's office fit-out, a fan coil often means a terminal unit on a four-pipe or two-pipe water system. A chiller, a heat pump or a boiler sits elsewhere.

CIBSE Journal's 2016 CPD module on fan coils describes the unit as a fan, at least one coil, controls and usually a filter, and notes that most fan coils recirculate room air rather than bringing in fresh air. Fresh air usually comes from a separate ventilation system. The rest of this page covers the water kind unless it says otherwise.

Fan coil unit types compared, with makers' published figures

The four casings below all hold the same parts. What changes is where the box sits, how far the air has to travel and how much of the unit you can see. A ceiling cassette sits in the ceiling grid with its grille on show and blows air out on four sides. A ceiling concealed (ducted) unit hides above the ceiling and sends air through ducts to grilles or slots. A floor console sits low on a wall, often under a window. A high-wall unit sits high on a wall and looks like a split indoor unit. Each row uses one maker's published data sheet so the numbers come from a real product range, not an average. Cooling is rated at room air of 27°C dry bulb and 19°C wet bulb with water entering at 7°C and leaving at 12°C on all three Daikin and Trane sheets. Ranges run from the smallest size at its lowest fan speed to the largest size at its highest, unless the row says high speed only. We have not tested any of these units.

Daikin's UK fan coil range page gives wider catalogue spans for the same four types: cassettes from 2.19 to 5.5 kW in a 600 x 600 mm panel (FWF-D) and 6.37 to 9.7 kW in a 900 x 900 mm panel (FWC-D); ducted ranges up to 24.73 kW (FWN) and up to 250 Pa of external static pressure (FWD); floor units from 1.50 to 7.78 kW (FWV); and wall units from 2.40 to 5.21 kW (FWT). Daikin's FWF-D cassette launch note, dated 24 January 2024, says it fits a standard 600 x 600 mm ceiling module, comes in 2-pipe or 4-pipe form, uses a brushless DC fan and has a drain pump with 835 mm lift.

Sound figures are not like for like across makers. Trane quotes sound pressure in the reverberant field of a 100 m³ room with 0.5 seconds of reverberation. Daikin quotes FWZ sound power to ISO 3741 and a sound pressure figure beside it. The FWB-BT flyer gives sound pressure at high speed without stating the room condition. Use the numbers to compare sizes within one range, and ask the designer for the figure at the speed the unit will actually run.

Fan coil unit types: one published range per type (makers' data sheets, checked 28 Nov 2026)
TypeRange used and fan motorCooling (kW)Airflow (m³/h)Sound pressure, dB(A)
Ceiling cassetteTrane CWS (AC motor) and CWE (EC motor), 2-pipe; 575 x 575 mm or 820 x 820 mm body1.27 to 11.1310 to 1,82024 to 51
Ceiling concealed (ducted)Daikin FWB-BT, 239 mm tall, up to 71 Pa available pressure; AC motor, 7 speeds2.61 to 10.34 (high speed)400 to 1,200 (high speed)44.5 to 57.5 (high speed)
Floor consoleDaikin FWZ-AT/AF, 564 mm tall, 226 mm deep; brushless DC motor1.35 to 4.48 (2-pipe)205 to 76328 to 54
High wallDaikin FWT-HT/HTV; brushless DC motor2.4 to 5.2Not in the brochureNot in the brochure

Two-pipe or four-pipe

A two-pipe fan coil has one coil and one flow and return. The whole circuit carries chilled water in summer and warm water in winter, so every unit on it cools or heats at the same time. A four-pipe unit has a cooling coil and a separate heating coil on two circuits, so one office can heat while the next one cools. CIBSE Journal notes that two-pipe changeover is usually manual and can be slow on a large system, and that four-pipe units run one coil at a time with a narrow dead band between them.

The same Trane cassette shows the trade-off. Sharing the casing with a second coil leaves less room for the cooling coil, so the four-pipe version cools less at the same airflow. For the full comparison, including when a refit can move from two-pipe to four-pipe, see our guide to two-pipe vs four-pipe fan coil units.

Trane CWS 05 cassette at high speed, 1,500 m³/h (Trane catalogue UNT-PRC011-E4, checked 28 Nov 2026)
2-pipe4-pipe
Cooling, water 7°C in, 12°C out9.51 kW7.71 kW
Heating11.7 kW, 50°C water through the same coil11 kW, 70°C in and 60°C out through a separate coil
Heat one room while cooling anotherNo, the circuit is in one modeYes

How the chilled or hot water reaches a fan coil

A water fan coil does not make its own cooling. It borrows it from plant elsewhere in the building. The chain runs like this:

  • 1. A chiller or an air-to-water heat pump makes chilled water. Makers rate fan coils with water entering at 7°C and leaving at 12°C, which is the usual design point.
  • 2. Pumps push that water through insulated pipes in risers and ceiling voids to each floor.
  • 3. At each fan coil a valve opens or closes the coil. The room thermostat or the building management system decides when, and sets the fan speed.
  • 4. The fan draws room air through the filter and across the cold coil. Cooled air leaves through the grille, slots or ducts.
  • 5. Moisture in the air condenses on the coil and drops into a tray, then leaves by gravity drain or a small pump. Trane's cassette pump lifts up to 650 mm.
  • 6. The water, now about 5°C warmer, returns to the plant to be cooled again.
  • 7. For heating, the same path carries warm water from a boiler or heat pump. On a two-pipe system it uses the same coil; on a four-pipe system it uses a second coil and a second pair of pipes.

Heating water temperatures, and why fan coils suit heat pumps

CIBSE Journal notes that traditional heating water ran at 82°C flow and 71°C return, that 80°C and 60°C became more common, and that lower flow temperatures suit heat pumps and let condensing boilers run in condensing mode. Hitachi's UK page on fan coils for heat pumps says its fan coils need 45°C water to give full heating capacity, where radiators may need up to 80°C, so they can run from heat pumps with a 60°C maximum. The fan is the reason: forcing air across the coil moves more heat out of cooler water than a radiator can by itself.

EC or AC fan motors

An AC fan coil motor runs at a few fixed speeds. Trane wires three of its six, and Daikin's FWB-BT has seven. Daikin's FWB-C ducted range, for example, uses a multi-speed AC motor with a permanently connected capacitor. An EC motor is a brushless DC motor with its own electronics, so it can run at any speed in its range and uses much less power at the low speeds where fan coils spend most of their time. CIBSE Journal puts EC motors at around 30% more efficient than AC motors. Trane claims 76% energy savings for its EC cassette on the typical loads of a Paris office building, and Daikin claims up to 70% for its brushless DC floor console against traditional motors. Those two are makers' claims for their own products.

Trane publishes the same cassette with both motors, so the difference can be read straight off its tables at the same airflow and the same cooling output.

Worked example, on our assumptions: 20 size-02 cassettes running at high speed for 2,500 hours a year. The EC version saves 37 W per unit, which is 740 W across the floor and about 1,850 kWh a year. That is fan power only. The chiller or heat pump uses far more than the fans, so ask for the whole system's figures too. Fan power per unit of air also matters for compliance: at 710 m³/h (about 197 litres a second), 68 W is about 0.35 W per l/s and 31 W is about 0.16 W per l/s. CIBSE Journal reported in 2016 that the Non-Domestic Building Services Compliance Guide set 0.5 W per l/s for fan coil units; check the current edition with your designer.

Fan power at the same airflow and cooling output, Trane 2-pipe cassette (catalogue UNT-PRC011-E4, checked 28 Nov 2026)
Size and speedAirflow (m³/h)Cooling (kW)AC motor, CWS (W)EC motor, CWE (W)
Size 01, speed 13101.84255
Size 04, speed 16304.213310
Size 02, speed 37104.336831

Fan coil vs VRF vs split

All three put a fan and a coil in the room. The difference is what travels to that coil. A chilled-water fan coil gets water, and the refrigerant stays in the plant. A VRF system, called VRV by Daikin, pipes refrigerant from one outdoor unit to many indoor units, and those indoor units are themselves often called fan coils. A split pipes refrigerant from one outdoor unit to one indoor unit, or a few on a multi-split.

CIBSE Journal's 2025 CPD module on VRF in hotel retrofits explains why the refrigerant matters. VRF pipework runs into occupied rooms, and BS EN IEC 60335-2-40:2024 treats the area around an indoor unit as the higher-risk zone, where leak detectors, automatic shut-off valves or extra ventilation may be needed with mildly flammable refrigerants such as R32. Its 150-room hotel example uses about a dozen VRF systems serving about 12 rooms each. A polyvalent heat pump uses water as the distribution medium, which reduces the refrigerant charge in occupied rooms, but switching an existing VRF hotel to it normally means replacing every fan coil and all the pipework.

This page does not compare prices. For installed costs, see our commercial air conditioning installation cost guide, and for the refrigerant side, our guides to VRF and VRV air conditioning and to chilled-water fan coils vs DX splits.

What each system sends to the room (CIBSE Journal, Designing Buildings, GOV.UK, checked 28 Nov 2026)
Chilled-water fan coilVRF (VRV)Split or multi-split
What runs to each roomWaterRefrigerantRefrigerant
PlantChiller or heat pump, often a boiler, plus pumpsOne outdoor unit serving many indoor unitsOne outdoor unit per indoor unit, or a few on a multi-split
Refrigerant in occupied roomsNone in the terminalYes, piped to every indoor unitYes, in each indoor unit
Heat one room, cool anotherYes on four-pipeYes on heat recovery systemsEach single split has its own outdoor unit
Who works on the room unitMechanical or water contractor; F-gas firm only for the plantF-gas certified companyF-gas certified company
Typical buildingsOffices and hotels with central plantOffices and hotels with many rooms and varying loadsHomes, small shops, single offices

Where fan coil units are used

CIBSE Journal notes that fan coils became the usual way to air condition UK office blocks in the 1980s, and that their use in homes is growing. Designing Buildings lists four common layouts: horizontal units hidden above a ceiling, where the ceiling helps cut noise; exposed horizontal units for an open-ceiling look in offices, restaurants and receptions; underfloor perimeter units to deal with draughts and sun on glazed facades; and vertical wall units for refurbishments with low ceilings. Hotels use them because each room needs its own control and the plant can sit on the roof or in the basement. For the room-level design in a hotel, see our guide to hotel guest room air conditioning.

For how a concealed unit is hung, ducted and given an access panel, see our guide to ceiling and ducted fan coil units. For what a service visit should cover, see our fan coil unit maintenance guide.

Houses, shops and floors that already have a chiller

A refrigerant fan coil, meaning a normal split indoor, suits houses, small shops, meeting rooms and single retail bays. You buy capacity per room, you put an outdoor unit somewhere lawful, and you live with pipe limits from that manufacturer. A water fan coil suits floors where a central plant already exists or where dozens of rooms must sit on one landlord system. Adding one rogue split in a plant room that was designed for water terminals can fight the building controls. The survey should say whether the base build already has chilled water.

  • Split indoor: refrigerant coil, outdoor condenser, F-gas install.
  • Water fan coil: chilled water and sometimes heating water from central plant.
  • Both need a condensate plan and filter access after the ceiling or the casing is finished.

Where a home might use a water fan coil

The usual case is a house with an air-to-water heat pump. Hitachi's UK range sells floor and ceiling convertible, ducted and cassette fan coils for homes, and says cooling needs a heat pump model that supports cooling. Fitted in a bedroom or a loft room, a fan coil can give heat from the same water as the radiators and some cooling in summer. Two cautions apply. Chilled-water pipes need insulation all the way so they do not drip inside walls and ceilings, and every unit that cools needs a condensate drain or pump. Hitachi says its units are certified as low as 17 dB(A), without naming the model or speed, so ask for the figure for the exact unit and speed.

If the house has no wet system, a split or multi-split usually does the same job with less pipework. Our guide to air-to-air vs air-to-water heat pumps sets out that choice.

Refrigerant in the coil, or water

The person who services a water terminal may never touch refrigerant. If your quote says fan coil and nothing else, ask which of those two worlds you are in. In everyday engineering language a wall-mounted split is a fan and a coil. In office specifications, fan coil usually means a water terminal. Make the quote say refrigerant split or water fan coil in plain words. The terminal itself often has no refrigerant. Any chiller, heat pump or split that does contain F-gas still needs certified people when that circuit is opened. GOV.UK sets out company certification for that work. Our guide to whether fan coil units use refrigerant covers DX fan coils, which carry refrigerant in a fan coil casing.

Two service sheets, one grille

Filters, drains and fans are common to both. Refrigerant checks, leak records and end-of-life recovery apply to the split and to any chiller that uses F-gas, under the operator rules on GOV.UK. A water coil adds pumps, valves, strainers and water treatment. Mixing those service sheets is how a facility manager pays twice. Noise and throw still decide comfort. A cassette that dumps air onto a desk, or a ducted fan coil with no access panel, fails whether the coil holds refrigerant or water. Ask for airflow, sound and a filter location you can actually reach. Trane publishes air throw for its cassettes of 3.0 to 5.5 metres with the louvres at 30 degrees, which is the kind of figure to ask for. Where the plant is large enough, GOV.UK also describes air conditioning inspections as a separate duty.

Stop when the quote will not say which coil

Stop and send the quote back if it will not name the terminal type, the medium in the coil, the cooling and heating capacity, the drain method and who maintains it after year one. For a split, ask for the outdoor model and the F-gas company who will install it. For a water unit, ask which plant it connects to, whether it is two-pipe or four-pipe, whether the fan motor is EC, and whether the building management system already has a point for it. If you are a tenant, check whether the fan coil is in your demise or the landlord's. That decides who instructs the survey. Swapping a water fan coil for a split cassette is sometimes possible if the building allows an outdoor unit, a pipe route and a drain, and if the landlord agrees. It is a new system, not a grille change.

Frequently asked questions

What is a fan coil unit in simple terms?

A fan, a coil and a filter in one box. The fan blows room air across the coil, and chilled or hot water in the coil cools or heats it. In offices and hotels the water comes from a central chiller, heat pump or boiler.

What sizes do fan coil units come in?

On the Daikin and Trane data sheets we read on 28 November 2026, single units run from about 1.3 to 11 kW of cooling and 200 to 1,800 m³/h of air. Daikin's largest ducted range goes to 24.73 kW.

What is a ducted fan coil unit?

A fan coil hidden above the ceiling that pushes air through ducts to grilles or slots. Daikin's FWB-BT, for example, is 239 mm tall and moves 400 to 1,200 m³/h at high speed with up to 71 Pa for the ductwork.

Are fan coil units noisy?

It depends on type, size and fan speed. Trane's cassettes are listed at 24 to 51 dB(A) and Daikin's ducted FWB-BT at 44.5 to 57.5 dB(A) at high speed, measured in different ways. Ask for the figure at the speed the unit will run.

What is the difference between a fan coil and VRF?

A chilled-water fan coil gets water, and the refrigerant stays in the plant. VRF pipes refrigerant to every indoor unit, which can mean leak detection in occupied rooms with mildly flammable refrigerants.

Can I use a fan coil unit at home?

Yes, usually with an air-to-water heat pump that can cool. Hitachi says its fan coils give full heating at 45°C water. Insulate chilled pipes and plan a condensate drain for every unit.

Does a water fan coil need an F-gas installer?

The terminal itself often has no refrigerant. Any chiller, heat pump or split that does contain F-gas still needs certified people when that circuit is opened. Ask which plant is in scope.

Can I swap a water fan coil for a split cassette?

Sometimes, if the building allows an outdoor unit, a pipe route and a drain, and if the landlord agrees. It is a new system, not a grille change. Survey both the base-build plant and the outdoor position first.

Core buying guides

Start with these high-intent guides, then dig into the rest of the library.

Related guides

More technology guides

Sources and further reading

How this guide was prepared

This guide was written by the Local AC Installers Editorial Team. We compare official guidance, legislation and established consumer information, separate general information from project-specific advice, and show publication dates and sources. We do not accept installer accreditation claims at face value.

Read our full editorial policy.

Get a quote

Get AC installation quotes

Start with the installation postcode and service. Add optional detail only if you have it.

Free, no obligationSubmit the form at no cost. You decide whether to accept any quote.

Local introductionsWe pass your enquiry to installers covering the postcode. Reply speed and volume both vary.

No lead sellingDetails go only to relevant installers for quote contact. See the privacy notice.

Ask each company for F-Gas registration and insurance. We introduce local installers.

Add more project detail (optional)

You choose whether to accept any quote. Read our installer checks and privacy notice.