Most 2.5 to 3.5 kW wall splits allow 10 to 15 m of height difference between the indoor and outdoor unit, and 12 m is the most common figure: across 10 small models in the makers' manuals and data books we read on 28 November 2026, the limit ran from 8 m (Samsung Wind-Free 09 and 12) to 15 m (Daikin Perfera RXM25R and RXM35R, and Fujitsu AOYG09KMCC). Every single-room split we read prints one figure that applies whether the outdoor unit is above or below the indoor unit, and some 5 kW models allow more, up to 20 m on the Daikin RXF50F and RXM50R. The maximum pipe length for the same small models is 15 to 25 m, and most leave the factory charged for 5 to 15 m of pipe, with 10 to 20 g of extra refrigerant per metre beyond that.

Height and pipe limits by model
These figures come from each maker's installation manual, service manual or technical data book, read on 28 November 2026. The height difference is the vertical distance between the indoor unit and the outdoor unit, not the length of pipe. Pre-charged length is how much pipe the factory charge covers; beyond it the installer adds the extra refrigerant shown. We have not tested any of these units. Always check the manual for the exact model being quoted, because limits change between capacities and generations.
We could not read a current UK installation manual for a Hisense wall split, so Hisense is not in the table. LG is left out too: the only LG installation document we could read was a general training guide that names no UK model. The Midea row is a Midea-made 9,000 and 12,000 BTU wall split sold in the UK (models CF-ET09A and CF-ET12A).
| Outdoor unit | Max pipe length | Max height difference | Pre-charged for | Extra refrigerant |
|---|---|---|---|---|
| Daikin Sensira RXF25F, RXF35F | 20 m | 12 m | 10 m | 20 g/m |
| Daikin RXF50F | 30 m | 20 m | 10 m | 20 g/m |
| Daikin Perfera RXM25R, RXM35R | 20 m | 15 m | 10 m | 20 g/m |
| Daikin RXM50R | 30 m | 20 m | Not stated in data book | 20 g/m over 10 m |
| Mitsubishi Electric MUZ-AY25/35/42/50VG | 20 m | 12 m | 7.5 m | 20 g/m |
| Mitsubishi Electric MUZ-LN25VG2, MUZ-LN35VG2 | 20 m | 12 m | 10 m | 20 g/m |
| Mitsubishi Electric MUZ-AP25/35/42VG | 20 m | 12 m | 10 m | 20 g/m |
| Toshiba Seiya RAS-10E2AVG-E, RAS-13E2AVG-E | 15 m | 12 m | 15 m | None needed |
| Toshiba Seiya RAS-16E2AVG-E, RAS-18E2AVG-E | 20 m | 12 m | 15 m | 20 g/m (max 100 g) |
| Fujitsu AOYG09KMCC | 20 m | 15 m | 15 m | 20 g/m |
| Panasonic CU-CZ25ZKE, CU-CZ35ZKE | 20 m (3 m min) | 10 m | 7.5 m | 10 g/m |
| Samsung Wind-Free AR09TX, AR12TX | 15 m (3 m min) | 8 m | 5 m | 15 g/m |
| Samsung Wind-Free AR18TX, AR24TX | 30 m (3 m min) | 15 m | 5 m | 15 g/m |
| Midea CF-ET09A, CF-ET12A | 25 m | 10 m | 5 m | 12 g/m |
What the numbers say for a 2.5 to 3.5 kW split
Across the 10 small models (2.5 to 3.5 kW, or 9,000 to 12,000 BTU), the height limit is 8 m on one, 10 m on two, 12 m on five and 15 m on two. The median is 12 m. If your rise is under 8 m, every small model we read can take it. Between 8 and 10 m, the Samsung Wind-Free 09 and 12 drop out. Between 10 and 12 m, Panasonic's CZ25ZKE and CZ35ZKE and the Midea CF-ET models drop out too. Over 12 m, only the Daikin Perfera RXM25R and RXM35R and the Fujitsu AOYG09KMCC are left, up to 15 m. Over 15 m, a small single split from these makers is out, and the options are a 5 kW outdoor unit with a 15 to 20 m limit or a different outdoor position.
Pipe length is a separate limit. A tall rise uses pipe as well as height, so a loft to garden run can pass the height test and still fail the length test on a model with a 15 m maximum, such as the Toshiba Seiya 10 and 13 or the Samsung Wind-Free 09 and 12.
Does it matter whether the outdoor unit is above or below?
For the single-room splits in the table, no. Daikin's data books print one maximum level difference for indoor to outdoor, Fujitsu's design manual covers both the indoor unit higher and the outdoor unit higher under one maximum, and Mitsubishi Electric, Toshiba, Panasonic, Samsung and Midea each print a single figure. So an outdoor unit on a flat roof above a top-floor flat has the same limit as an outdoor unit in the garden below a loft bedroom.
Direction does matter on some larger systems. Mitsubishi Electric's PUMY-SM112 to SM140 multi-room outdoor units, for example, allow 50 m when the outdoor unit is higher than the indoor units and 40 m when it is lower. If you are being quoted a multi-split or a commercial system, ask which line of the manual the installer has used.
Worked example: loft bedroom, outdoor unit on the ground
Take a two-storey house with a loft conversion. Say each storey measures 2.7 m floor to floor, the indoor unit is fixed about 2.0 m above the loft floor, and the outdoor unit sits on a 0.3 m stand in the garden. The rise is 2.7 + 2.7 + 2.0 minus 0.3, which is 7.1 m. These are example measurements, not standard ones: measure your own house, because ceiling heights vary.
At 7.1 m, every small model in the table passes the height limit. The tightest is the Samsung Wind-Free 09 or 12, with 0.9 m to spare. Now the pipe: 7.1 m up the wall, about 3 m across the loft and 1.5 m at the two ends gives roughly 12 m. That is inside every model's maximum length. The extra refrigerant then differs by model: none on the Toshiba Seiya 10 or the Fujitsu AOYG09KMCC (both pre-charged to 15 m), 40 g on the Daikin RXF35F ((12 minus 10) x 20 g), 45 g on the Panasonic CZ25ZKE ((12 minus 7.5) x 10 g), 90 g on the Mitsubishi Electric MUZ-AY35VG (its own table gives 90 g at 12 m) and 105 g on the Samsung AR09TX ((12 minus 5) x 15 g). The extra charge is the installer's job and is part of a normal quote for a run this long.
Now move the same loft bedroom into a three-storey townhouse with the outdoor unit in a basement front area about 2.5 m below the pavement. The rise becomes 2.7 x 3 + 2.0 + 2.5, roughly 12.6 m. That is past the 12 m limit on the Daikin Sensira RXF35F, the Mitsubishi Electric AY, LN and AP, and the Toshiba Seiya. It is still inside the 15 m of the Daikin Perfera RXM35R and the Fujitsu AOYG09KMCC, or the outdoor unit can move to a higher spot.
Why makers set a height limit
Oil travels round the circuit with the refrigerant and has to return to the compressor. A tall rise makes that harder, and a long column of liquid refrigerant changes the pressure at the far end. That is why the manual prints a maximum height difference alongside the maximum length. Extra refrigerant for a long run does not buy extra height, and a larger pipe chosen on site does not raise the limit either. Diameter, height and length all come from the same manual, and commissioning stays with an F-gas certified company.
What to give the installer when you ask for a price
Say which floor the indoor unit will be on and where you want the outdoor unit, and say which one is higher. If you can, measure the vertical distance between the two spots. A ground-floor room with the outdoor unit just outside is rarely a height problem. Loft rooms, top-floor flats with a garden unit, and basement areas under tall houses are the usual near-misses.
If either the height or the length is past the limit in the manual, change the outdoor position or the model. A short drop onto a wall the outdoor unit is not allowed on is not a solution: in England, Planning Portal permitted development conditions still cover noise, boundaries and the rest.
Frequently asked questions
What is the maximum height difference between the indoor and outdoor unit?
For most 2.5 to 3.5 kW wall splits it is 10 to 15 m, with 12 m the most common figure in the manuals we read. The range was 8 m (Samsung Wind-Free 09 and 12) to 15 m (Daikin Perfera RXM, Fujitsu AOYG09KMCC). Some 5 kW models allow 20 m.
Can the outdoor unit be higher than the indoor unit?
Yes. For the single-room splits we read, the same height limit applies whether the outdoor unit is above or below the indoor unit. Some multi-room systems have different figures for each direction, such as Mitsubishi Electric's PUMY-SM (50 m outdoor higher, 40 m outdoor lower).
Is height difference the same as pipe length?
No. Height difference is the vertical distance between the two units. Pipe length is the full run of pipe, including the horizontal parts. Both have their own limit in the manual, and a run has to pass both.
Does adding refrigerant let me go higher?
No. Extra refrigerant is for pipe beyond the pre-charged length, up to the maximum length. It does not raise the maximum height difference.
Is 10 m or 20 m the UK maximum?
There is no UK legal maximum. The limit is set by the maker for each outdoor unit. Among the small models we read, it ran from 8 to 15 m, and up to 20 m on some 5 kW units.
Core buying guides
Start with these high-intent guides, then dig into the rest of the library.
Related guides
More technology guides
Sources and further reading
- Daikin: RXF-F technical data book EEDEN25A (checked 28 Nov 2026)
- Daikin: RXF20-42F installer reference guide 4P769827-15G (checked 28 Nov 2026)
- Daikin: RXM-R technical data book EEDEN20 (checked 28 Nov 2026)
- Mitsubishi Electric: MSZ/MUZ-AY25-50VG(K) service manual OBH932 (checked 28 Nov 2026)
- Mitsubishi Electric: MSZ-LN VG2 installation manual, Australian edition, same outdoor model (checked 28 Nov 2026)
- Mitsubishi Electric: MSZ-AP22-50VGKD installation manual, Australian edition, same outdoor model (checked 28 Nov 2026)
- Mitsubishi Electric UK: PUMY-SM112-140 installation manual (checked 28 Nov 2026)
- Toshiba: RAS-B05-B18E2KVG-E / RAS-05-18E2AVG-E service manual SVM-21112 (checked 28 Nov 2026)
- Fujitsu General: ASYG07-14KMCC design and technical manual (checked 28 Nov 2026)
- Panasonic: CS/CU-CZ25ZKE, CZ35ZKE service manual PAPAMY2306065CE (checked 28 Nov 2026)
- Samsung: RAC technical data book, AR**TX Wind-Free, Europe (checked 28 Nov 2026)
- Midea: CF-ET09A, CF-ET12A owner's and installation manual (checked 28 Nov 2026)
- GOV.UK: certification for companies working on equipment containing F-gas
- Planning Portal: air source heat pumps
How this guide was prepared
This guide was written by the Local AC Installers Editorial Team. We compare official guidance, legislation and established consumer information, separate general information from project-specific advice, and show publication dates and sources. We do not accept installer accreditation claims at face value.