Free tool

Air conditioning fault code lookup

Choose a brand and type the code on your display. 188 codes for 9 brands, with the usual causes and whether to try a safe check or call an engineer.

  • 188 codes
  • Checked against manufacturer documentation

188 codes across 9 brands

Daikin fault codes

How to read Daikin codes
CodeMeaning and usual causesWhat to do
A1Indoor unit circuit board fault
Power surge, moisture or a failed indoor PCB
Book an engineer
A3Drain level problem
Blocked condensate drain, failed drain pump or float switch
Book an engineer
A5Freeze-up protection or high-pressure control
Blocked filters, low airflow, dirty coil or a faulty heat exchanger sensor
Try safe checks first
A6Indoor fan motor fault
Seized or failed fan motor, loose connector or PCB fault
Book an engineer
C4Indoor heat exchanger temperature sensor fault
Failed or disconnected thermistor
Book an engineer
C9Room (suction air) temperature sensor fault
Failed or disconnected thermistor
Book an engineer
E1Outdoor unit circuit board fault
Failed outdoor PCB, power disturbance
Book an engineer
E3High-pressure protection activated
Blocked outdoor coil or airflow, outdoor fan fault, overcharge
Try safe checks first
E5Compressor overload
Low refrigerant, blocked airflow, valve or compressor fault
Book an engineer
E6Compressor lock
Compressor failed to start: electrical or mechanical compressor fault
Switch off and call an engineer
E7Outdoor fan motor lock
Obstruction in the fan, failed fan motor or PCB
Try safe checks first
F3Discharge pipe temperature too high
Low refrigerant from a leak, blocked circuit or sensor fault
Book an engineer
H6Compressor position sensor fault
Compressor wiring, inverter board or compressor fault
Book an engineer
H9Outdoor air temperature sensor fault
Failed or disconnected thermistor
Book an engineer
J3Discharge pipe temperature sensor fault
Failed or disconnected thermistor
Book an engineer
J6Outdoor heat exchanger temperature sensor fault
Failed or disconnected thermistor
Book an engineer
L4Inverter heat sink temperature too high
Blocked outdoor airflow, fan fault or inverter board fault
Try safe checks first
L5Inverter output overcurrent
Compressor or inverter board fault
Switch off and call an engineer
U0Refrigerant shortage
A refrigerant leak, or a closed service valve after installation
Book an engineer
U2Supply voltage problem
Low or unstable mains voltage, wiring or inverter fault
Book an engineer
U4Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
Try safe checks first
UAIndoor and outdoor unit mismatch
Incompatible units connected or wrong settings after installation
Book an engineer

Mitsubishi Electric fault codes

How to read Mitsubishi Electric codes
CodeMeaning and usual causesWhat to do
P1Intake (room air) temperature sensor fault
Failed or disconnected thermistor
Book an engineer
P2Pipe (liquid) temperature sensor fault
Failed or disconnected thermistor
Book an engineer
P4Drain sensor or float switch fault
Drain sensor fault or float switch connector open
Book an engineer
P5Drain pump fault or drain overflow
Blocked drain, failed drain pump
Book an engineer
P6Freezing or overheating protection
Blocked filters, low airflow, dirty coil or low refrigerant
Try safe checks first
P8Pipe temperature abnormal
Refrigerant shortage, sensor fault or wiring fault
Book an engineer
P9Pipe (two-phase) temperature sensor fault
Failed or disconnected thermistor
Book an engineer
E0Remote controller transmission error
Controller wiring, address or controller fault
Book an engineer
E3Remote controller transmission error
Controller wiring, address or controller fault
Book an engineer
E6Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
Try safe checks first
E7Communication error between indoor and outdoor units
Interconnecting cable fault or indoor controller board fault
Book an engineer

Panasonic fault codes

How to read Panasonic codes
CodeMeaning and usual causesWhat to do
H11Communication error between indoor and outdoor units
Interconnecting cable fault, power disturbance or PCB fault
Try safe checks first
H14Indoor intake air temperature sensor fault
Failed or disconnected sensor
Book an engineer
H15Compressor temperature sensor fault
Failed or disconnected sensor
Book an engineer
H16Outdoor current transformer open circuit
Low refrigerant, or outdoor PCB or current transformer fault
Book an engineer
H19Indoor fan motor locked
Obstructed or failed fan motor, indoor PCB fault
Book an engineer
H27Outdoor air temperature sensor fault
Failed or disconnected sensor
Book an engineer
H97Outdoor fan motor locked
Obstruction in the fan, failed fan motor or outdoor PCB
Try safe checks first
H99Indoor freeze prevention protection
Blocked filters, low airflow, dirty coil or low refrigerant
Try safe checks first
F91Refrigeration cycle abnormal
Low refrigerant from a leak, or a closed valve
Book an engineer
F99Outdoor DC peak (overcurrent) detected
Compressor or outdoor PCB fault
Switch off and call an engineer

LG fault codes

How to read LG codes
CodeMeaning and usual causesWhat to do
CH01Indoor temperature sensor fault
Sensor open or short circuit
Book an engineer
CH02Indoor inlet pipe sensor fault
Sensor open or short circuit
Book an engineer
CH05Communication error between indoor and outdoor units (E0 on some models)
Interconnecting cable fault, power interruption or PCB fault
Try safe checks first
CH10Indoor fan fault (E6 on some models)
Obstructed or failed indoor fan motor
Book an engineer
CH38Low refrigerant (F4 on some models)
A refrigerant leak
Book an engineer
CH61Overheating of the outdoor unit in cooling, or the indoor unit in heating
Dirty filters, blocked airflow around the outdoor unit, dirty coil
Try safe checks first
CH04Drainage problem (shown as FL on some models)
Blocked condensate drain or drain pump fault
Try safe checks first
CH07Operating mode conflict between indoor units
One indoor unit is set to heat while another is set to cool or dry on a shared outdoor unit
Try safe checks first
CH34Same as CH61: overheating protection
Blocked airflow around the outdoor unit in cooling, or dirty filters in heating
Try safe checks first
CH53Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
Try safe checks first
CH54Reverse phase detected on the power supply
Supply wiring fault, often after electrical work
Book an engineer
CH66Communication cable or pipe connection problem between the units
Wiring or piping fault, usually after installation or relocation
Book an engineer
CH67Outdoor fan fault (shown as EF on some models)
Debris, snow or ice blocking the outdoor fan, or a failed fan motor
Try safe checks first
CH90Protection stop during the test run
Piping connection or refrigerant problem found at commissioning
Book an engineer
CH91Protection stop during the test run
Piping connection or refrigerant problem found at commissioning
Book an engineer
CH93Communication error between indoor and outdoor units
Power or interconnecting cable fault; on models from 2021 both units need power
Try safe checks first

Samsung fault codes

How to read Samsung codes
CodeMeaning and usual causesWhat to do
E101Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
Try safe checks first
E121Indoor room temperature sensor fault
Failed or disconnected sensor
Book an engineer
E122Indoor pipe (evaporator) temperature sensor fault
Failed or disconnected sensor
Book an engineer
E154Indoor fan motor fault
Obstructed or failed fan motor, PCB fault
Book an engineer
E416Discharge temperature too high
Low refrigerant from a leak, blocked circuit or sensor fault
Book an engineer
E464Inverter module (IPM) overcurrent
Compressor or outdoor inverter board fault
Switch off and call an engineer
E554Refrigerant leak detected
Low refrigerant charge from a leak
Book an engineer
E163Indoor circuit board memory (EEPROM) error
Incorrect or lost data on the main control board
Book an engineer
CFFilter cleaning reminder (not a fault)
The filter timer has run out
Try safe checks first
CIAuto clean running (not a fault)
Auto clean starts when the unit is switched off and can be turned off on the remote
Try safe checks first
dFDefrost in progress (not a fault)
Heating mode is clearing ice from the outdoor unit; the indoor fan pauses
Try safe checks first

Fujitsu fault codes

How to read Fujitsu codes
CodeMeaning and usual causesWhat to do
11Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
On the unit: Operation lamp 1 flash, timer lamp 1 flash, economy lamp flashing
Try safe checks first
12Wired remote controller communication error
Controller cable, connection or controller fault
On the unit: Operation lamp 1 flash, timer lamp 2 flashes, economy lamp flashing
Book an engineer
14Network communication error
Network adapter, controls wiring or address fault
On the unit: Operation lamp 1 flash, timer lamp 4 flashes, economy lamp flashing
Book an engineer
15Test run not completed
Commissioning test run was not finished after installation
On the unit: Operation lamp 1 flash, timer lamp 5 flashes, economy lamp flashing
Book an engineer
16Transmission or peripheral connection error
Fault in a connected accessory or its wiring
On the unit: Operation lamp 1 flash, timer lamp 6 flashes, economy lamp flashing
Book an engineer
21Refrigerant circuit address setting error
Wrong address settings on a multi-unit system
On the unit: Operation lamp 2 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
22Indoor unit capacity error
Connected indoor capacity does not suit the outdoor unit
On the unit: Operation lamp 2 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
23Combination error
Incompatible indoor and outdoor units connected
On the unit: Operation lamp 2 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
24Connected unit number error
Too many or too few units connected for the system
On the unit: Operation lamp 2 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
26Address setting error
Duplicate or wrong unit address
On the unit: Operation lamp 2 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
27Master and slave unit set-up error
Group control settings are wrong
On the unit: Operation lamp 2 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
29Unit number error in the wired controller circuit
Too many units on one wired controller
On the unit: Operation lamp 2 flashes, timer lamp 9 flashes, economy lamp flashing
Book an engineer
31Power supply interruption
A power cut or momentary supply drop
On the unit: Operation lamp 3 flashes, timer lamp 1 flash, economy lamp flashing
Try safe checks first
32Indoor circuit board memory (EEPROM) error
Indoor PCB fault
On the unit: Operation lamp 3 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
35Manual auto switch error
The manual auto button on the indoor unit is stuck or faulty
On the unit: Operation lamp 3 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
3AIndoor unit wired controller communication error
Controller cable or indoor PCB fault
On the unit: Operation lamp 3 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
41Room (inlet air) temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 4 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
42Indoor heat exchanger temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 4 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
51Indoor fan motor fault
Obstructed or failed fan motor, or PCB fault
On the unit: Operation lamp 5 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
52Indoor expansion valve fault
Expansion valve coil or wiring fault
On the unit: Operation lamp 5 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
53Drain pump fault
Blocked condensate drain, failed pump or float switch
On the unit: Operation lamp 5 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
57Damper fault
Damper motor or wiring fault on ducted units
On the unit: Operation lamp 5 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
58Intake grille fault
Auto-lift grille motor or switch fault
On the unit: Operation lamp 5 flashes, timer lamp 8 flashes, economy lamp flashing
Book an engineer
5UIndoor unit fault
An indoor fault that needs the service code read with tools
On the unit: Operation lamp 5 flashes, timer lamp 15 flashes, economy lamp flashing
Book an engineer
62Outdoor circuit board or communication fault
Outdoor PCB or internal wiring fault
On the unit: Operation lamp 6 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
63Inverter fault
Inverter board or compressor drive fault
On the unit: Operation lamp 6 flashes, timer lamp 3 flashes, economy lamp flashing
Switch off and call an engineer
64Active filter or PFC circuit fault
Outdoor power circuit fault or unstable supply
On the unit: Operation lamp 6 flashes, timer lamp 4 flashes, economy lamp flashing
Switch off and call an engineer
65Trip terminal L error
Outdoor protection circuit fault
On the unit: Operation lamp 6 flashes, timer lamp 5 flashes, economy lamp flashing
Switch off and call an engineer
6ADisplay board communication fault
Display PCB or its cable
On the unit: Operation lamp 6 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
71Outdoor discharge temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
72Compressor temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
73Outdoor heat exchanger liquid temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
74Outdoor air temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
75Outdoor suction temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
76Service valve temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
77Outdoor heat sink temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
82Sub-cooling temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 8 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
83Outdoor liquid pipe temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 8 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
84Outdoor current sensor fault
Outdoor PCB current sensing fault
On the unit: Operation lamp 8 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
86Pressure sensor or pressure switch fault
Failed sensor or switch, or a pressure problem
On the unit: Operation lamp 8 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
94Outdoor current trip
Compressor overcurrent: compressor, inverter or supply fault
On the unit: Operation lamp 9 flashes, timer lamp 4 flashes, economy lamp flashing
Switch off and call an engineer
95Compressor rotor position detection fault
Compressor or inverter board fault
On the unit: Operation lamp 9 flashes, timer lamp 5 flashes, economy lamp flashing
Switch off and call an engineer
97Outdoor fan motor fault
Obstruction in the fan, failed fan motor or PCB
On the unit: Operation lamp 9 flashes, timer lamp 7 flashes, economy lamp flashing
Try safe checks first
98Second outdoor fan motor fault
Obstruction in the fan, failed fan motor or PCB
On the unit: Operation lamp 9 flashes, timer lamp 8 flashes, economy lamp flashing
Try safe checks first
994-way valve fault
Reversing valve or coil fault, so heating or cooling cannot switch
On the unit: Operation lamp 9 flashes, timer lamp 9 flashes, economy lamp flashing
Book an engineer
9AExpansion valve coil fault
Coil or wiring fault on the outdoor expansion valve
On the unit: Operation lamp 9 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
9UOutdoor unit fault
An outdoor fault that needs the service code read with tools
On the unit: Operation lamp 9 flashes, timer lamp 15 flashes, economy lamp flashing
Book an engineer
A1Discharge temperature too high
Low refrigerant from a leak, blocked circuit or sensor fault
On the unit: Operation lamp 10 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
A3Compressor temperature too high
Low refrigerant, blocked airflow or compressor fault
On the unit: Operation lamp 10 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
A4High pressure fault
Blocked outdoor coil or airflow, fan fault or overcharge
On the unit: Operation lamp 10 flashes, timer lamp 4 flashes, economy lamp flashing
Try safe checks first
A5Low pressure fault
Low refrigerant from a leak or a closed valve
On the unit: Operation lamp 10 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
J1Branch box fault (VRF systems)
Branch box board or wiring fault
On the unit: Operation lamp 13 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
J2Multi-split branch box fault
Branch box board or wiring fault
On the unit: Operation lamp 13 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer

Mitsubishi Heavy Industries fault codes

How to read Mitsubishi Heavy Industries codes
CodeMeaning and usual causesWhat to do
E3Signal transmission error between indoor and outdoor units
Power supply problem, broken signal wire or indoor or outdoor PCB fault
Try safe checks first
E5Signal transmission error between indoor and outdoor units
Power supply problem, broken signal wire or indoor or outdoor PCB fault
Try safe checks first
E9Drain error
Failed drain pump, broken pump wire or float switch fault
Book an engineer
E16Indoor fan motor fault
Failed fan motor or poor connector connection
Book an engineer
E35High pressure protection in cooling
Overload, overcharge, outdoor coil sensor fault or a closed service valve
Try safe checks first
E36Compressor overheating
Low refrigerant, discharge sensor fault or a closed service valve
Book an engineer
E37Outdoor heat exchanger sensor fault
Broken sensor wire, poor connection or outdoor PCB fault
Book an engineer
E38Outdoor air temperature sensor fault
Broken sensor wire, poor connection or outdoor PCB fault
Book an engineer
E39Discharge pipe sensor fault
Broken sensor wire, poor connection or outdoor PCB fault
Book an engineer
E40Running with the gas-side service valve closed
Service valve left closed after installation, or outdoor PCB fault
Switch off and call an engineer
E42Compressor current cut
Compressor locked, open phase, power transistor short or closed service valve
Switch off and call an engineer
E47Active filter voltage error
Wrong supply voltage or outdoor PCB fault
Book an engineer
E48Outdoor fan motor fault
Obstruction in the fan, failed fan motor or poor connection
Try safe checks first
E51Power transistor fault
Inverter or main PCB fault
Switch off and call an engineer
E53Outdoor suction sensor fault
Broken sensor wire, poor connection or outdoor sub-PCB fault
Book an engineer
E57Refrigerant cycle protection
Low refrigerant from a leak, or a closed service valve
Book an engineer
E58Current safe stop
Overload operation, overcharge or a locked compressor
Book an engineer
E59Outdoor unit fault stop
Broken compressor wire or a blocked compressor
Switch off and call an engineer
E60Compressor rotor lock
Compressor fault, open phase or outdoor PCB fault
Switch off and call an engineer

Haier fault codes

How to read Haier codes
CodeMeaning and usual causesWhat to do
E1Indoor room temperature sensor fault
Failed or disconnected sensor
Book an engineer
E2Indoor pipe temperature sensor fault
Failed or disconnected sensor
Book an engineer
E4Indoor circuit board memory (EEPROM) fault
Indoor PCB fault
Book an engineer
E5Indoor anti-frost protection
Blocked filters, low airflow or low refrigerant
Book an engineer
E7Communication fault between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
Book an engineer
E9Indoor unit overload in heating
Blocked airflow, dirty filters or overcharge
Book an engineer
E14Indoor fan motor fault
Obstructed or failed fan motor, or PCB fault
Book an engineer
F1Inverter power module (IPM) protection
Compressor drive or outdoor board fault
Switch off and call an engineer
F2Compressor overcurrent
Compressor, inverter or supply fault
Switch off and call an engineer
F3Communication error between the power module and main board
Outdoor board or internal wiring fault
Book an engineer
F4Compressor discharge temperature protection
Low refrigerant from a leak, blocked circuit or sensor fault
Book an engineer
F6Outdoor air temperature sensor fault
Failed or disconnected sensor
Book an engineer
F7Suction temperature sensor fault
Failed or disconnected sensor
Book an engineer
F8Outdoor DC fan motor fault
Obstruction in the fan or a failed fan motor
Book an engineer
F9Power module reset
Supply disturbance or outdoor board fault
Book an engineer
F11Compressor loss of synchronism
Compressor or inverter fault
Switch off and call an engineer
F12Outdoor circuit board memory (EEPROM) fault
Outdoor PCB fault
Book an engineer
F13Lack of refrigerant
A refrigerant leak
Book an engineer
F144-way valve reversing fault
Reversing valve or coil fault
Book an engineer
F19Supply over or under voltage protection
Unstable mains supply or wiring fault
Book an engineer
F20High pressure protection
Blocked outdoor airflow, fan fault or overcharge
Book an engineer
F21Outdoor coil temperature sensor fault
Failed or disconnected sensor
Book an engineer
F22Outdoor AC overcurrent protection
Supply, compressor or board fault
Switch off and call an engineer
F23Compressor phase overcurrent (U, V or W phase)
Compressor winding or inverter fault
Switch off and call an engineer
F24Current transformer detection fault
Outdoor board current sensing fault
Book an engineer
F25Compressor discharge sensor fault
Failed or disconnected sensor
Book an engineer
F27Compressor current sampling circuit fault
Outdoor board fault
Book an engineer
F28Compressor position detection circuit fault
Outdoor board or compressor fault
Switch off and call an engineer
F35Compressor driver board fault
Inverter driver board failure
Switch off and call an engineer
F43Model matching fault
Incompatible indoor and outdoor units or wrong board
Book an engineer
FERefrigerant leak detection fault (fixed-speed units)
Low refrigerant charge from a leak
Book an engineer

Gree fault codes

How to read Gree codes
CodeMeaning and usual causesWhat to do
E1High pressure protection
Dirty coils, a restriction in the circuit or overcharge
Try safe checks first
E3Low pressure protection
Dirty filters or coils, or low refrigerant from a leak
Book an engineer
E5Overcurrent protection
High or unstable supply voltage
Book an engineer
E6Communication error between indoor and outdoor units
Wrong, spliced or damaged interconnecting cable, or a board fault
Try safe checks first
E7Mode conflict
Indoor units on a shared outdoor unit set to different modes
Try safe checks first
F1Indoor room temperature sensor fault
Failed or disconnected sensor
Book an engineer
F2Indoor evaporator temperature sensor fault
Failed or disconnected sensor
Book an engineer
F3Outdoor air temperature sensor fault
Failed or disconnected sensor
Book an engineer
F4Outdoor pipe temperature sensor fault
Failed or disconnected sensor
Book an engineer
F5Discharge temperature sensor fault
Failed or disconnected sensor
Book an engineer
H1Defrosting (not a fault)
Heating mode is clearing ice from the outdoor unit
Try safe checks first
H5Inverter power module (IPM) protection
Supply voltage or compressor drive fault
Switch off and call an engineer
C5Jumper cap fault
Missing jumper, often after a control board was replaced
Book an engineer
U3DC bus voltage drop
Unstable or low mains supply
Book an engineer
L9Power protection
A power surge or supply fault
Book an engineer

Toshiba, Hitachi, Midea and Hisense

These brands do not publish a code list we could confirm against manufacturer documentation, so the lookup does not guess at meanings. Here is how to read the code so an engineer can diagnose it.

Toshiba

Toshiba wall units flash the indoor lamps when a fault is stored. Point the remote at the unit, press CHECK with the tip of a pencil, then press the timer up or down button to step through the codes. The unit beeps continuously and every lamp flashes when the display reaches the stored code, a two-character code such as 0C. Pressing CLR clears it. Give that code and the model number to an engineer: Toshiba's service manuals print the code table as segment graphics that vary by model, so we do not list meanings here. Source: Toshiba service manual SVM-09030: self-diagnosis by remote controller.

Hitachi

Hitachi wall units usually report a fault by blinking the timer lamp a set number of times, and the outdoor board shows a matching LED pattern. Count the blinks, note the model number from the indoor unit label and give both to an engineer. Blink meanings differ between ranges, so use the self-diagnosis table in the manual for your model.

Midea

Midea units show a two-character code such as E1 or P1 on the indoor display. The same code means different things across Midea ranges and the brands it builds for, so check the troubleshooting page of the manual for your model before acting on it.

Hisense

Hisense units show the code on the indoor display, and some wired controllers show a different code for the same fault. Meanings vary by series, so use the manual for your model or give the code and model number to an engineer.

A fault code tells you which part of the system has reported a problem, not always what caused it. Use the code to decide whether to try the safe checks or to switch off and call an engineer.

What the three actions mean

  • Try safe checks first Switch the unit off, clean the filters, clear anything blocking the indoor and outdoor units, then switch off at the isolator for five minutes and restart once. If the code returns, book an engineer.
  • Book an engineer This needs testing with instruments. Note the code, model and when it started, then book an F-gas qualified engineer. Do not keep resetting the unit.
  • Switch off and call an engineer Switch the system off at the isolator and leave it off. Running it can damage the compressor. Book an F-gas qualified engineer.

Before you call an engineer

  • Write down the exact code, the brand and the model number from the indoor unit label.
  • Note what the unit was doing: cooling or heating, and whether it happened after a power cut.
  • Check the filters and that nothing blocks the indoor or outdoor unit.
  • Take photos of the outdoor unit and any water marks.

Fault codes by brand

Related repair guides

How this list was compiled

Each meaning was checked against manufacturer manuals and support pages on 15 November 2026, and the Fujitsu, Mitsubishi Heavy Industries, Haier and Gree lists, plus the extra LG and Samsung codes, on 21 November 2026. Where sources disagreed, the code was left out. Meanings can differ between model ranges, so confirm against the manual for your unit. Sources are listed on each brand page.

Frequently asked questions

How do I find the fault code on my air conditioner?

It depends on the brand. Daikin, Panasonic and Toshiba use a diagnosis mode on the remote. LG, Samsung, Haier and Gree show the code on the indoor unit display. Fujitsu and Mitsubishi Heavy Industries flash the indoor lamps in a pattern, and Mitsubishi Electric shows the code on a wired controller or as a lamp pattern. Each brand page explains the steps.

Can I fix an air conditioning fault code myself?

You can safely clean the filters, clear obstructions around both units and restart the system once at the isolator. Anything involving electrics, sensors, the compressor or refrigerant needs an F-gas qualified engineer.

Should I keep resetting the unit?

No. One restart is reasonable. If the code comes back, repeated resets can damage the compressor and hide the evidence an engineer needs.

Why is my code not listed?

We only list codes whose meaning is confirmed by manufacturer documentation. Codes also vary by model. Check the manual for your unit or give the code and model number to an engineer.

How much does it cost to fix a fault?

Most repairs start with a diagnosis visit, often in the low hundreds of pounds or less in 2026 illustrations, before parts or refrigerant work. Ask what the callout fee includes.

More free tools

Get a quote

Get air conditioning repair quotes near you

Start with the installation postcode and service. Add optional detail only if you have it.

Free, no obligationSubmit the form at no cost. You decide whether to accept any quote.

Local introductionsWe pass your enquiry to installers covering the postcode. Reply speed and volume both vary.

No lead sellingDetails go only to relevant installers for quote contact. See the privacy notice.

Ask each company for F-Gas registration and insurance. We introduce local installers.

Add more project detail (optional)

You choose whether to accept any quote. Read our installer checks and privacy notice.