A traditional fan coil unit does not contain refrigerant. It is a fan blowing air over a coil filled with chilled or hot water from a chiller, boiler or heat pump in the plant room. Refrigerant only appears in that central plant. Some manufacturers also sell 'DX fan coils', which are refrigerant indoor units for split or VRF systems. Look for water pipes and valves (water) or two thin insulated copper pipes and no water valves (refrigerant).

Water-based fan coils
In a chilled-water building, a chiller on the roof or in the plant room cools water to around 6 to 12°C and pumps it round the building. Each fan coil unit blows room air across a coil carrying that water. The air cools, the water warms slightly and returns to the chiller.
The fan coil itself holds only water, valves, a fan, a filter and a condensate tray. A leak from a fan coil is a water leak. That is why ceiling drips under fan coils are almost always condensate or a valve weeping, not refrigerant.
DX fan coils and split indoor units
DX stands for direct expansion. In a DX system the refrigerant itself flows to the indoor unit and evaporates in its coil. Wall splits, cassettes, ducted units and VRF indoor units are all DX. Some product ranges label these as fan coils, especially ducted ones.
A DX indoor unit carries refrigerant, so leaks are refrigerant leaks. The system's charge decides whether periodic F-gas leak checks are a legal requirement, and only certified engineers can open the circuit.
| Clue | Water fan coil | DX unit |
|---|---|---|
| Pipes at the unit | Flow and return water pipes with valves | Two copper pipes, one thin and one thick |
| Valves | Two- or three-port valves with actuators | No water valves; expansion valve inside |
| Central plant | Chiller, boiler or air-to-water heat pump | Outdoor condensing units |
| Leak type | Water | Refrigerant |
| F-gas leak checks | Not on the unit; on the chiller | Depends on the system charge |
Why it matters
Maintenance contracts are priced differently. Water fan coils need filters, trays, valves and water treatment. DX systems need those plus refrigerant leak checks and records where the charge requires them.
It also matters for refits. Moving from a water system to VRF puts refrigerant pipes through occupied floors, and larger systems may need leak detection in small rooms. Moving the other way puts water in the ceiling. A designer weighs both.
Frequently asked questions
Do fan coil units contain refrigerant?
Water-based fan coil units do not; they carry chilled or hot water. DX units, sometimes called DX fan coils, do contain refrigerant.
Do fan coil units need F-gas checks?
Water fan coils do not. The chiller or heat pump making the chilled water does, if its charge is above the threshold.
What temperature is the water in a fan coil unit?
Chilled water commonly flows around 6 to 12°C depending on design. Heating water for fan coils is usually low temperature, often 40 to 60°C.
Is VRF a fan coil system?
VRF indoor units do the same job but carry refrigerant instead of water. Some brands call their ducted VRF units fan coils.
Core buying guides
Start with these high-intent guides, then dig into the rest of the library.
Related guides
More technology guides
Sources and further reading
How this guide was prepared
This guide was written by the Local AC Installers Editorial Team. We compare official guidance, legislation and established consumer information, separate general information from project-specific advice, and show publication dates and sources. We do not accept installer accreditation claims at face value.