Most UK office fan coil units are concealed in the ceiling void. Each unit draws room air through a return grille or an open plenum, passes it over a water coil and pushes it through short insulated ducts to grilles or linear slot diffusers. The checks that matter are void depth, a clear fall for the condensate, an access panel under every unit and duct runs short enough to keep noise down.

Suspended office ceiling with linear diffusers

What a concealed fan coil installation looks like

A horizontal concealed unit hangs on drop rods from the slab. A typical unit is around 250 to 300 mm deep, so the void needs room for the unit, its condensate tray, the valves and the duct connections, usually 350 mm or more once lighting and sprinklers are counted.

Supply air leaves through a plenum box into flexible or rigid ducts and out through ceiling diffusers. Return air comes back either through a ducted grille or through the open ceiling void, called a plenum return. Plenum returns are cheaper but pull dust from the void and need tidy ceilings.

Ducted fan coils with longer runs can serve rooms away from the unit, which helps with quiet rooms such as meeting rooms or bedrooms in hotels. Every metre of duct adds resistance, so the unit must be selected for the real duct run, not the catalogue figure at zero pressure.

Points to check before the ceiling closes

Most problems with ceiling fan coils come from details that are invisible once the tiles go back.

  • An access panel or removable tile under every unit, filter and valve set
  • A condensate drain with a steady fall, or a pump where gravity is not possible
  • A secondary drip tray under valves where a leak would reach the ceiling
  • Pipe insulation that is continuous to stop condensation on chilled pipes
  • Flexible duct pulled taut and short, not coiled
  • Units kept away from the quiet end of meeting rooms where fan noise matters

Ceiling fan coils compared with cassettes

A cassette sits flush in the ceiling and blows straight out of its own face. It is easier to fit, but you see it and hear it. A concealed fan coil hides above the ceiling and lets the designer place discreet diffusers anywhere in the room.

In water-based buildings, the choice is often concealed fan coils for open offices and cassettes in small rooms. In split or VRF buildings, the indoor units come in both forms: ducted units are the refrigerant equivalent of a concealed fan coil.

Concealed fan coils and cassettes
PointConcealed fan coilCassette
Visible in the roomGrilles or slots onlyFull face panel
Ceiling void neededDeeper, plus duct spaceAbout 250 to 300 mm clear
Noise in the roomLower when ducts are long enoughFan heard at the panel
Maintenance accessThrough a panel or tileThrough the front grille
Good fitOpen offices, hotels, quiet roomsShops, small offices, single rooms

Commissioning and handover

Each unit should be water-balanced so that the far end of the floor gets its share of flow, and air-balanced so diffusers deliver what the design asks for. Ask for the balancing records with the handover pack.

Controls are the other weak point. Check which controller each unit answers to, whether it links to a building management system and what the setpoints and deadbands are. Fan coils fighting each other, one heating and one cooling in the same open space, is a common and wasteful fault.

Frequently asked questions

How deep a ceiling void does a fan coil unit need?

Many horizontal units are 250 to 300 mm deep, and the void usually needs 350 mm or more once ducts, valves, drainage and other services are added. Check the selected unit's drawings.

Are ceiling fan coils noisy?

A well-selected unit running at a sensible fan speed with enough duct between it and the diffuser is quiet. Noise usually comes from undersized units on high speed or from diffusers too close to the unit.

What does a ducted fan coil unit mean?

It is a concealed unit that pushes air through ducts to remote grilles or diffusers, rather than blowing straight into the room from its own face.

Why do ceiling fan coils leak?

Usually a blocked condensate tray or drain, failed pump, or condensation on chilled pipes where the insulation has gaps. A drip tray under the valves and regular drain checks prevent most leaks.

Core buying guides

Start with these high-intent guides, then dig into the rest of the library.

Related guides

More commercial guides

Sources and further reading

How this guide was prepared

This guide was written by the Local AC Installers Editorial Team. We compare official guidance, legislation and established consumer information, separate general information from project-specific advice, and show publication dates and sources. We do not accept installer accreditation claims at face value.

Read our full editorial policy.

Get a quote

Get AC installation quotes

Start with the installation postcode and service. Add optional detail only if you have it.

Free, no obligationSubmit the form at no cost. You decide whether to accept any quote.

Local introductionsWe pass your enquiry to installers covering the postcode. Reply speed and volume both vary.

No lead sellingDetails go only to relevant installers for quote contact. See the privacy notice.

Ask each company for F-Gas registration and insurance. We introduce local installers.

Add more project detail (optional)

You choose whether to accept any quote. Read our installer checks and privacy notice.