Fujitsu wall units report a fault by flashing the lamps on the indoor unit: count the flashes of the operation lamp and the timer lamp while the economy lamp flashes continuously. The two counts give the code, so 1 and 1 is code 11. A wired remote controller shows the same code directly on its screen.
Fujitsu fault code list
| Code | Meaning and usual causes | What to do |
|---|---|---|
| 11 | Communication error between indoor and outdoor units Interconnecting cable fault, power interruption or PCB fault On the unit: Operation lamp 1 flash, timer lamp 1 flash, economy lamp flashing | Try safe checks first |
| 12 | Wired remote controller communication error Controller cable, connection or controller fault On the unit: Operation lamp 1 flash, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 14 | Network communication error Network adapter, controls wiring or address fault On the unit: Operation lamp 1 flash, timer lamp 4 flashes, economy lamp flashing | Book an engineer |
| 15 | Test run not completed Commissioning test run was not finished after installation On the unit: Operation lamp 1 flash, timer lamp 5 flashes, economy lamp flashing | Book an engineer |
| 16 | Transmission or peripheral connection error Fault in a connected accessory or its wiring On the unit: Operation lamp 1 flash, timer lamp 6 flashes, economy lamp flashing | Book an engineer |
| 21 | Refrigerant circuit address setting error Wrong address settings on a multi-unit system On the unit: Operation lamp 2 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| 22 | Indoor unit capacity error Connected indoor capacity does not suit the outdoor unit On the unit: Operation lamp 2 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 23 | Combination error Incompatible indoor and outdoor units connected On the unit: Operation lamp 2 flashes, timer lamp 3 flashes, economy lamp flashing | Book an engineer |
| 24 | Connected unit number error Too many or too few units connected for the system On the unit: Operation lamp 2 flashes, timer lamp 4 flashes, economy lamp flashing | Book an engineer |
| 26 | Address setting error Duplicate or wrong unit address On the unit: Operation lamp 2 flashes, timer lamp 6 flashes, economy lamp flashing | Book an engineer |
| 27 | Master and slave unit set-up error Group control settings are wrong On the unit: Operation lamp 2 flashes, timer lamp 7 flashes, economy lamp flashing | Book an engineer |
| 29 | Unit number error in the wired controller circuit Too many units on one wired controller On the unit: Operation lamp 2 flashes, timer lamp 9 flashes, economy lamp flashing | Book an engineer |
| 31 | Power supply interruption A power cut or momentary supply drop On the unit: Operation lamp 3 flashes, timer lamp 1 flash, economy lamp flashing | Try safe checks first |
| 32 | Indoor circuit board memory (EEPROM) error Indoor PCB fault On the unit: Operation lamp 3 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 35 | Manual auto switch error The manual auto button on the indoor unit is stuck or faulty On the unit: Operation lamp 3 flashes, timer lamp 5 flashes, economy lamp flashing | Book an engineer |
| 3A | Indoor unit wired controller communication error Controller cable or indoor PCB fault On the unit: Operation lamp 3 flashes, timer lamp 10 flashes, economy lamp flashing | Book an engineer |
| 41 | Room (inlet air) temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 4 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| 42 | Indoor heat exchanger temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 4 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 51 | Indoor fan motor fault Obstructed or failed fan motor, or PCB fault On the unit: Operation lamp 5 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| 52 | Indoor expansion valve fault Expansion valve coil or wiring fault On the unit: Operation lamp 5 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 53 | Drain pump fault Blocked condensate drain, failed pump or float switch On the unit: Operation lamp 5 flashes, timer lamp 3 flashes, economy lamp flashing | Book an engineer |
| 57 | Damper fault Damper motor or wiring fault on ducted units On the unit: Operation lamp 5 flashes, timer lamp 7 flashes, economy lamp flashing | Book an engineer |
| 58 | Intake grille fault Auto-lift grille motor or switch fault On the unit: Operation lamp 5 flashes, timer lamp 8 flashes, economy lamp flashing | Book an engineer |
| 5U | Indoor unit fault An indoor fault that needs the service code read with tools On the unit: Operation lamp 5 flashes, timer lamp 15 flashes, economy lamp flashing | Book an engineer |
| 62 | Outdoor circuit board or communication fault Outdoor PCB or internal wiring fault On the unit: Operation lamp 6 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 63 | Inverter fault Inverter board or compressor drive fault On the unit: Operation lamp 6 flashes, timer lamp 3 flashes, economy lamp flashing | Switch off and call an engineer |
| 64 | Active filter or PFC circuit fault Outdoor power circuit fault or unstable supply On the unit: Operation lamp 6 flashes, timer lamp 4 flashes, economy lamp flashing | Switch off and call an engineer |
| 65 | Trip terminal L error Outdoor protection circuit fault On the unit: Operation lamp 6 flashes, timer lamp 5 flashes, economy lamp flashing | Switch off and call an engineer |
| 6A | Display board communication fault Display PCB or its cable On the unit: Operation lamp 6 flashes, timer lamp 10 flashes, economy lamp flashing | Book an engineer |
| 71 | Outdoor discharge temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| 72 | Compressor temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 73 | Outdoor heat exchanger liquid temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 3 flashes, economy lamp flashing | Book an engineer |
| 74 | Outdoor air temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 4 flashes, economy lamp flashing | Book an engineer |
| 75 | Outdoor suction temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 5 flashes, economy lamp flashing | Book an engineer |
| 76 | Service valve temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 6 flashes, economy lamp flashing | Book an engineer |
| 77 | Outdoor heat sink temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 7 flashes, timer lamp 7 flashes, economy lamp flashing | Book an engineer |
| 82 | Sub-cooling temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 8 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
| 83 | Outdoor liquid pipe temperature sensor fault Failed or disconnected thermistor On the unit: Operation lamp 8 flashes, timer lamp 3 flashes, economy lamp flashing | Book an engineer |
| 84 | Outdoor current sensor fault Outdoor PCB current sensing fault On the unit: Operation lamp 8 flashes, timer lamp 4 flashes, economy lamp flashing | Book an engineer |
| 86 | Pressure sensor or pressure switch fault Failed sensor or switch, or a pressure problem On the unit: Operation lamp 8 flashes, timer lamp 6 flashes, economy lamp flashing | Book an engineer |
| 94 | Outdoor current trip Compressor overcurrent: compressor, inverter or supply fault On the unit: Operation lamp 9 flashes, timer lamp 4 flashes, economy lamp flashing | Switch off and call an engineer |
| 95 | Compressor rotor position detection fault Compressor or inverter board fault On the unit: Operation lamp 9 flashes, timer lamp 5 flashes, economy lamp flashing | Switch off and call an engineer |
| 97 | Outdoor fan motor fault Obstruction in the fan, failed fan motor or PCB On the unit: Operation lamp 9 flashes, timer lamp 7 flashes, economy lamp flashing | Try safe checks first |
| 98 | Second outdoor fan motor fault Obstruction in the fan, failed fan motor or PCB On the unit: Operation lamp 9 flashes, timer lamp 8 flashes, economy lamp flashing | Try safe checks first |
| 99 | 4-way valve fault Reversing valve or coil fault, so heating or cooling cannot switch On the unit: Operation lamp 9 flashes, timer lamp 9 flashes, economy lamp flashing | Book an engineer |
| 9A | Expansion valve coil fault Coil or wiring fault on the outdoor expansion valve On the unit: Operation lamp 9 flashes, timer lamp 10 flashes, economy lamp flashing | Book an engineer |
| 9U | Outdoor unit fault An outdoor fault that needs the service code read with tools On the unit: Operation lamp 9 flashes, timer lamp 15 flashes, economy lamp flashing | Book an engineer |
| A1 | Discharge temperature too high Low refrigerant from a leak, blocked circuit or sensor fault On the unit: Operation lamp 10 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| A3 | Compressor temperature too high Low refrigerant, blocked airflow or compressor fault On the unit: Operation lamp 10 flashes, timer lamp 3 flashes, economy lamp flashing | Book an engineer |
| A4 | High pressure fault Blocked outdoor coil or airflow, fan fault or overcharge On the unit: Operation lamp 10 flashes, timer lamp 4 flashes, economy lamp flashing | Try safe checks first |
| A5 | Low pressure fault Low refrigerant from a leak or a closed valve On the unit: Operation lamp 10 flashes, timer lamp 5 flashes, economy lamp flashing | Book an engineer |
| J1 | Branch box fault (VRF systems) Branch box board or wiring fault On the unit: Operation lamp 13 flashes, timer lamp 1 flash, economy lamp flashing | Book an engineer |
| J2 | Multi-split branch box fault Branch box board or wiring fault On the unit: Operation lamp 13 flashes, timer lamp 2 flashes, economy lamp flashing | Book an engineer |
What the three actions mean
- Try safe checks first Switch the unit off, clean the filters, clear anything blocking the indoor and outdoor units, then switch off at the isolator for five minutes and restart once. If the code returns, book an engineer.
- Book an engineer This needs testing with instruments. Note the code, model and when it started, then book an F-gas qualified engineer. Do not keep resetting the unit.
- Switch off and call an engineer Switch the system off at the isolator and leave it off. Running it can damage the compressor. Book an F-gas qualified engineer.
What to tell the engineer
- The exact code and when it first appeared.
- The model number from the indoor unit label, and roughly when it was installed.
- Whether it happens in cooling, heating or both.
- Who installed it and whether it is under warranty.
More Fujitsu help
- Fujitsu air conditioning review
- Air conditioning repair: faults, callout costs and engineers
- Why is my air conditioning not cooling?
- Air conditioning regas cost
- What voids an air conditioning warranty
Other brands
- Daikin fault codes
- Mitsubishi Electric fault codes
- Panasonic fault codes
- LG fault codes
- Samsung fault codes
- Mitsubishi Heavy Industries fault codes
- Haier fault codes
- Gree fault codes
- Search all fault codes
Frequently asked questions
How do I read a Fujitsu fault code?
Fujitsu wall units report a fault by flashing the lamps on the indoor unit: count the flashes of the operation lamp and the timer lamp while the economy lamp flashes continuously. The two counts give the code, so 1 and 1 is code 11. A wired remote controller shows the same code directly on its screen.
What does Fujitsu 11 mean?
11 is a communication error between the indoor and outdoor units. Usual causes: interconnecting cable fault, power interruption or pcb fault. Switch the unit off, clean the filters, clear anything blocking the indoor and outdoor units, then switch off at the isolator for five minutes and restart once. If the code returns, book an engineer.
What does Fujitsu 21 mean?
21 means refrigerant circuit address setting error. A sealed system does not use up refrigerant, so this points to a leak that an F-gas qualified engineer must find and repair before recharging.
Can I reset a Fujitsu air conditioner to clear a code?
Switch the unit off, turn it off at the isolator for five minutes and restart it once. If the code returns, stop resetting it and book an engineer. Repeated resets can damage the compressor.
Why is my Fujitsu code not on this list?
Only codes confirmed by manufacturer documentation are listed, and meanings vary by model. These codes come from Fujitsu General UK's fault code sheet, which covers domestic splits, light commercial and VRF systems. Codes 14, 21 to 29 and J1 to J2 mostly apply to multi-unit and VRF systems. Check the manual for your unit or give the code and model number to an engineer.