Fault code lookup

Fujitsu air conditioning fault codes

53 Fujitsu error codes with their meaning, usual causes and what to do next.

  • 53 codes
  • Checked 21 November 2026
Fault codes

Fujitsu wall units report a fault by flashing the lamps on the indoor unit: count the flashes of the operation lamp and the timer lamp while the economy lamp flashes continuously. The two counts give the code, so 1 and 1 is code 11. A wired remote controller shows the same code directly on its screen.

Fujitsu fault code list

Fujitsu air conditioning fault codes
CodeMeaning and usual causesWhat to do
11Communication error between indoor and outdoor units
Interconnecting cable fault, power interruption or PCB fault
On the unit: Operation lamp 1 flash, timer lamp 1 flash, economy lamp flashing
Try safe checks first
12Wired remote controller communication error
Controller cable, connection or controller fault
On the unit: Operation lamp 1 flash, timer lamp 2 flashes, economy lamp flashing
Book an engineer
14Network communication error
Network adapter, controls wiring or address fault
On the unit: Operation lamp 1 flash, timer lamp 4 flashes, economy lamp flashing
Book an engineer
15Test run not completed
Commissioning test run was not finished after installation
On the unit: Operation lamp 1 flash, timer lamp 5 flashes, economy lamp flashing
Book an engineer
16Transmission or peripheral connection error
Fault in a connected accessory or its wiring
On the unit: Operation lamp 1 flash, timer lamp 6 flashes, economy lamp flashing
Book an engineer
21Refrigerant circuit address setting error
Wrong address settings on a multi-unit system
On the unit: Operation lamp 2 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
22Indoor unit capacity error
Connected indoor capacity does not suit the outdoor unit
On the unit: Operation lamp 2 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
23Combination error
Incompatible indoor and outdoor units connected
On the unit: Operation lamp 2 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
24Connected unit number error
Too many or too few units connected for the system
On the unit: Operation lamp 2 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
26Address setting error
Duplicate or wrong unit address
On the unit: Operation lamp 2 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
27Master and slave unit set-up error
Group control settings are wrong
On the unit: Operation lamp 2 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
29Unit number error in the wired controller circuit
Too many units on one wired controller
On the unit: Operation lamp 2 flashes, timer lamp 9 flashes, economy lamp flashing
Book an engineer
31Power supply interruption
A power cut or momentary supply drop
On the unit: Operation lamp 3 flashes, timer lamp 1 flash, economy lamp flashing
Try safe checks first
32Indoor circuit board memory (EEPROM) error
Indoor PCB fault
On the unit: Operation lamp 3 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
35Manual auto switch error
The manual auto button on the indoor unit is stuck or faulty
On the unit: Operation lamp 3 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
3AIndoor unit wired controller communication error
Controller cable or indoor PCB fault
On the unit: Operation lamp 3 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
41Room (inlet air) temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 4 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
42Indoor heat exchanger temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 4 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
51Indoor fan motor fault
Obstructed or failed fan motor, or PCB fault
On the unit: Operation lamp 5 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
52Indoor expansion valve fault
Expansion valve coil or wiring fault
On the unit: Operation lamp 5 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
53Drain pump fault
Blocked condensate drain, failed pump or float switch
On the unit: Operation lamp 5 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
57Damper fault
Damper motor or wiring fault on ducted units
On the unit: Operation lamp 5 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
58Intake grille fault
Auto-lift grille motor or switch fault
On the unit: Operation lamp 5 flashes, timer lamp 8 flashes, economy lamp flashing
Book an engineer
5UIndoor unit fault
An indoor fault that needs the service code read with tools
On the unit: Operation lamp 5 flashes, timer lamp 15 flashes, economy lamp flashing
Book an engineer
62Outdoor circuit board or communication fault
Outdoor PCB or internal wiring fault
On the unit: Operation lamp 6 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
63Inverter fault
Inverter board or compressor drive fault
On the unit: Operation lamp 6 flashes, timer lamp 3 flashes, economy lamp flashing
Switch off and call an engineer
64Active filter or PFC circuit fault
Outdoor power circuit fault or unstable supply
On the unit: Operation lamp 6 flashes, timer lamp 4 flashes, economy lamp flashing
Switch off and call an engineer
65Trip terminal L error
Outdoor protection circuit fault
On the unit: Operation lamp 6 flashes, timer lamp 5 flashes, economy lamp flashing
Switch off and call an engineer
6ADisplay board communication fault
Display PCB or its cable
On the unit: Operation lamp 6 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
71Outdoor discharge temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
72Compressor temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
73Outdoor heat exchanger liquid temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
74Outdoor air temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
75Outdoor suction temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
76Service valve temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
77Outdoor heat sink temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 7 flashes, timer lamp 7 flashes, economy lamp flashing
Book an engineer
82Sub-cooling temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 8 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer
83Outdoor liquid pipe temperature sensor fault
Failed or disconnected thermistor
On the unit: Operation lamp 8 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
84Outdoor current sensor fault
Outdoor PCB current sensing fault
On the unit: Operation lamp 8 flashes, timer lamp 4 flashes, economy lamp flashing
Book an engineer
86Pressure sensor or pressure switch fault
Failed sensor or switch, or a pressure problem
On the unit: Operation lamp 8 flashes, timer lamp 6 flashes, economy lamp flashing
Book an engineer
94Outdoor current trip
Compressor overcurrent: compressor, inverter or supply fault
On the unit: Operation lamp 9 flashes, timer lamp 4 flashes, economy lamp flashing
Switch off and call an engineer
95Compressor rotor position detection fault
Compressor or inverter board fault
On the unit: Operation lamp 9 flashes, timer lamp 5 flashes, economy lamp flashing
Switch off and call an engineer
97Outdoor fan motor fault
Obstruction in the fan, failed fan motor or PCB
On the unit: Operation lamp 9 flashes, timer lamp 7 flashes, economy lamp flashing
Try safe checks first
98Second outdoor fan motor fault
Obstruction in the fan, failed fan motor or PCB
On the unit: Operation lamp 9 flashes, timer lamp 8 flashes, economy lamp flashing
Try safe checks first
994-way valve fault
Reversing valve or coil fault, so heating or cooling cannot switch
On the unit: Operation lamp 9 flashes, timer lamp 9 flashes, economy lamp flashing
Book an engineer
9AExpansion valve coil fault
Coil or wiring fault on the outdoor expansion valve
On the unit: Operation lamp 9 flashes, timer lamp 10 flashes, economy lamp flashing
Book an engineer
9UOutdoor unit fault
An outdoor fault that needs the service code read with tools
On the unit: Operation lamp 9 flashes, timer lamp 15 flashes, economy lamp flashing
Book an engineer
A1Discharge temperature too high
Low refrigerant from a leak, blocked circuit or sensor fault
On the unit: Operation lamp 10 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
A3Compressor temperature too high
Low refrigerant, blocked airflow or compressor fault
On the unit: Operation lamp 10 flashes, timer lamp 3 flashes, economy lamp flashing
Book an engineer
A4High pressure fault
Blocked outdoor coil or airflow, fan fault or overcharge
On the unit: Operation lamp 10 flashes, timer lamp 4 flashes, economy lamp flashing
Try safe checks first
A5Low pressure fault
Low refrigerant from a leak or a closed valve
On the unit: Operation lamp 10 flashes, timer lamp 5 flashes, economy lamp flashing
Book an engineer
J1Branch box fault (VRF systems)
Branch box board or wiring fault
On the unit: Operation lamp 13 flashes, timer lamp 1 flash, economy lamp flashing
Book an engineer
J2Multi-split branch box fault
Branch box board or wiring fault
On the unit: Operation lamp 13 flashes, timer lamp 2 flashes, economy lamp flashing
Book an engineer

These codes come from Fujitsu General UK's fault code sheet, which covers domestic splits, light commercial and VRF systems. Codes 14, 21 to 29 and J1 to J2 mostly apply to multi-unit and VRF systems. Meanings can vary by model, so confirm against the manual for your unit.

What the three actions mean

  • Try safe checks first Switch the unit off, clean the filters, clear anything blocking the indoor and outdoor units, then switch off at the isolator for five minutes and restart once. If the code returns, book an engineer.
  • Book an engineer This needs testing with instruments. Note the code, model and when it started, then book an F-gas qualified engineer. Do not keep resetting the unit.
  • Switch off and call an engineer Switch the system off at the isolator and leave it off. Running it can damage the compressor. Book an F-gas qualified engineer.

What to tell the engineer

  • The exact code and when it first appeared.
  • The model number from the indoor unit label, and roughly when it was installed.
  • Whether it happens in cooling, heating or both.
  • Who installed it and whether it is under warranty.

More Fujitsu help

Other brands

Frequently asked questions

How do I read a Fujitsu fault code?

Fujitsu wall units report a fault by flashing the lamps on the indoor unit: count the flashes of the operation lamp and the timer lamp while the economy lamp flashes continuously. The two counts give the code, so 1 and 1 is code 11. A wired remote controller shows the same code directly on its screen.

What does Fujitsu 11 mean?

11 is a communication error between the indoor and outdoor units. Usual causes: interconnecting cable fault, power interruption or pcb fault. Switch the unit off, clean the filters, clear anything blocking the indoor and outdoor units, then switch off at the isolator for five minutes and restart once. If the code returns, book an engineer.

What does Fujitsu 21 mean?

21 means refrigerant circuit address setting error. A sealed system does not use up refrigerant, so this points to a leak that an F-gas qualified engineer must find and repair before recharging.

Can I reset a Fujitsu air conditioner to clear a code?

Switch the unit off, turn it off at the isolator for five minutes and restart it once. If the code returns, stop resetting it and book an engineer. Repeated resets can damage the compressor.

Why is my Fujitsu code not on this list?

Only codes confirmed by manufacturer documentation are listed, and meanings vary by model. These codes come from Fujitsu General UK's fault code sheet, which covers domestic splits, light commercial and VRF systems. Codes 14, 21 to 29 and J1 to J2 mostly apply to multi-unit and VRF systems. Check the manual for your unit or give the code and model number to an engineer.

Sources

Get a quote

Get Fujitsu repair quotes near you

Start with the installation postcode and service. Add optional detail only if you have it.

Free, no obligationSubmit the form at no cost. You decide whether to accept any quote.

Local introductionsWe pass your enquiry to installers covering the postcode. Reply speed and volume both vary.

No lead sellingDetails go only to relevant installers for quote contact. See the privacy notice.

Ask each company for F-Gas registration and insurance. We introduce local installers.

Add more project detail (optional)

You choose whether to accept any quote. Read our installer checks and privacy notice.